High Current AC Solid State Relay
Product Overview
The High Current AC Solid State Relay switches larger compatible AC loads under an external controller's command. The HX series reference identifies the relevant products. Its role is the power connection between the supply and load, with electronic switching in place of moving contacts. The actual operating version depends on the load duty and installation, rather than on the largest current number in a series name.
At higher currents, the surrounding connections are an important part of the assembly. Terminals, conductors and the cooling path all carry the effects of sustained operation. A poor contact can create local heating even when the relay itself has a suitable rating. Startup demand and the switching cycle also differ between loads. The product's input must match the controller separately from its output requirements. Together, these details define a working power switch within the cabinet, with the heatsink and main connections supporting its intended duty.
Features
Bolt Installation-Module Type Single AC Solid State Relay
One-way SCR chip antiparallel NO output
DC-AC DC signal control AC load
Optoelectronic devices Isolation
Zero crossing / Random Trigger Form
Built-in RC absorbing circuit
LED Status Indicator







Product Parameters
Electrical · Mechanical · Thermal
| Parameter | Value |
|---|---|
| Product model | HX □ -L |
| Control voltage | 3-32VDC |
| Control current | 6-25mA |
| Reverse voltage | 32VDC |
| Guarantee close voltage | 1VDC |
| Guarantee open voltage | 3VDC |
| Load voltage | 75-480VAC |
| Load max current | 60A-200A |
| Load mini current | 0.1A |
| Breakover voltage | ≤2VAC |
| Output leakage current | ≤8mA |
| Medium withstand voltage | ≥2500VAC |
| Insulating resistance | ≥100MΩ |
| Switching time | ≤10mS |
| Frequency range | 50-60Hz |
| Operating temperature | -20-70°C |
| Load current safety factor | resistive load 50-60%; inductive load 30-40% |
Bolt Installation-Module Type Single AC Solid State Relay
One-way SCR chip antiparallel NO output
DC-AC DC signal control AC load
Optoelectronic devices Isolation
Zero crossing / Random Trigger Form
Built-in RC absorbing circuit
LED Status Indicator
| Parameter | Value |
|---|---|
| Product model | HX □ -L |
| Control voltage | 3-32VDC |
| Control current | 6-25mA |
| Reverse voltage | 32VDC |
| Guarantee close voltage | 1VDC |
| Guarantee open voltage | 3VDC |
| Load voltage | 75-480VAC |
| Load max current | 160A-300A |
| Load mini current | 0.2A |
| Breakover voltage | ≤2VAC |
| Output leakage current | ≤8mA |
| Medium withstand voltage | ≥2500VAC |
| Insulating resistance | ≥100MΩ |
| Switching time | ≤10mS |
| Frequency range | 50-60Hz |
| Operating temperature | -20-70°C |
| Load current safety factor | resistive load 50-60%; inductive load 30-40% |
Bolt Installation-Module Type Single AC Solid State Relay
One-way SCR chip antiparallel NO output
DC-AC DC signal control AC load
Optoelectronic devices Isolation
Zero crossing / Random Trigger Form
Built-in RC absorbing circuit
LED Status Indicator
| Parameter | Value |
|---|---|
| Product model | HX □ -L |
| Control voltage | 3-32VDC |
| Control current | 6-25mA |
| Reverse voltage | 32VDC |
| Guarantee close voltage | 1VDC |
| Guarantee open voltage | 3VDC |
| Load voltage | 75-480VAC |
| Load max current | 300A-400A |
| Load mini current | 0.2A |
| Breakover voltage | ≤2VAC |
| Output leakage current | ≤8mA |
| Medium withstand voltage | ≥2500VAC |
| Insulating resistance | ≥100MΩ |
| Switching time | ≤10mS |
| Frequency range | 50-60Hz |
| Operating temperature | -20-70°C |
| Load current safety factor | resistive load 50-60%; inductive load 30-40% |
Bolt Installation-Module Type High Power AC Solid State Relay
One-way crimp SCR chip antiparallel NO output
DC-AC DC signal control AC load
Optoelectronic devices Isolation
Zero crossing / Random Trigger Form
| Parameter | Value |
|---|---|
| Product model | HX □ -L |
| Control voltage | 3-32VDC |
| Control current | 6-25mA |
| Reverse voltage | 32VDC |
| Guarantee close voltage | 1VDC |
| Guarantee open voltage | 3VDC |
| Load voltage | 75-480VAC |
| Load max current | 400A-500A |
| Load mini current | 0.3A |
| Breakover voltage | ≤3VAC |
| Output leakage current | ≤1mA |
| Medium withstand voltage | ≥2500VAC |
| Insulating resistance | ≥100MΩ |
| Switching time | ≤10mS |
| Frequency range | 50-60Hz |
| Operating temperature | -20-70°C |
| Load current safety factor | resistive load 50-60%; inductive load 30-40% |
Typical Application
Where this module is used




Customized
Factory-direct flexibility
Product Highlights
FAQ
Common questions
Q: Does choosing a higher current model allow a smaller heatsink?
A: Not automatically. Cooling must be assessed from the losses, ambient conditions and product requirements.
Q: Why provide startup current as well as running current?
A: Some loads impose a substantial energization event that steady current alone does not describe.