Three Phase AC Voltage Regulator
Product Overview
The Three Phase AC Voltage Regulator is designed to provide stepless AC power adjustment for three-phase industrial loads. Instead of converting the supply to DC, the regulator changes the effective AC voltage by controlling the firing angle of the thyristor power stage. This makes the Three Phase AC Voltage Regulator suitable for processes that need repeatable adjustment of heating intensity, transformer input or other AC load power. Isolated control electronics separate low-voltage command signals from the main power circuit, while manual or analog control can be selected according to the equipment control scheme.
Packaging Instructions
Main-circuit range: three-phase 100~450 VAC.
Control power supply: 100~240 VAC.
The module provides 12 VDC, 500 mA for fan power and can interface with the company's RS485 communication module when computer-connected control or upgrading is required.
No phase-sequence restriction is required by the stated design, which simplifies field wiring and servicing.
Soft start is built in with a factory setting of 2 seconds to reduce power-on surge stress on the module and load.
An 85°C internal temperature protection function is included.
Typical Applications
The Three Phase AC Voltage Regulator can be applied to industrial electric heaters, furnace heating zones, transformer primary-side power control, lighting regulation, welding equipment, electroplating machinery and compatible three-phase motor-control applications. It is especially relevant where the process requires adjustable AC voltage rather than a rectified DC output.
Product Parameters
Electrical · Mechanical · Thermal
|
Parameter |
Nominal current |
Max.working current |
Interdiction voltage of SCR |
Frequency |
Dv/dt |
Di/dt |
Breaking leakage current(Max.) |
Making voltage drop(Max.) |
Insulating voltage (terminal/soleplate) |
Weight |
|
Unit |
Arms |
Arms |
Vpk |
Hz |
V/sec |
A/sec |
mA rms |
V rms |
V rms |
kg |
|
Value
|
50 |
3x50 |
1200 |
50/60 |
500 |
100 |
≤8 |
1.6 |
≥2500 |
0.425 |
|
70 |
3x70 |
1200 |
50/60 |
500 |
100 |
≤10 |
1.6 |
≤2500 |
0.425 |
|
|
120 |
3x120 |
1200 |
50/60 |
500 |
100 |
≤10 |
1.8 |
≤2500 |
0.425 |
|
|
200 |
3x200 |
1200 |
50/60 |
500 |
100 |
≤10 |
1.8 |
≤2500 |
0.425 |
|
|
250 |
3x250 |
1200 |
50/60 |
500 |
100 |
≤15 |
1.8 |
≤2500 |
2.2 |
|
|
350 |
3x350 |
1200 |
50/60 |
500 |
100 |
≤15 |
1.8 |
≤2500 |
2.2 |
|
|
500 |
3x500 |
1200 |
50/60 |
500 |
100 |
≤20 |
1.8 |
≤2500 |
2.2 |
|
Function |
Input voltage range |
Power supply |
Control voltage |
Control current |
Resistance of manual potentiomete |
Cooling |
Ambient temperature |
Output voltage |
|
Arms |
mA |
VDC |
mA |
KΩ |
m/s |
°C |
VDC |
|
|
Thyristor three phase AC phase shift voltage adjusting |
40~440V |
12V/400 |
0-5 |
4-20 |
10 |
air cooling heatsink, wind speed≥6 |
-30~+40 |
0-513 |
Typical Application
Where this module is used




Customized
Factory-direct flexibility
Product Highlights
FAQ
Common questions
Q: What should be checked before connecting a star or delta load?
A: Confirm the selected model's permitted load connection, supply arrangement and any neutral-wire requirement before installation.
Q: Is the Three Phase AC Voltage Regulator intended to produce DC power?
A: No. Its primary function is adjustable three-phase AC voltage control. Applications that require controlled DC output should be matched to a controlled rectifier module.
Hot Tags: three phase ac voltage regulator, China three phase ac voltage regulator manufacturers, suppliers, factory, Motor Forward Reverse Solid State Relay, Single Phase AC Voltage Regulator, Single Phase Controlled Rectifier, Three Phase Controlled Rectifier, Three Phase Motor Reversing Relay, Three Phase Rectifier Controller
Request a Quote